FCC Lompoc of Bureau of Prisons posted this Combined Synopsis/Solicitation on Nov 5, 2026. Responses are due Nov 16, 2026. NAICS 332321 (Metal Window and Door Manufacturing), product or service code 1290 (Miscellaneous Fire Control Equipment). Set-aside: Total Small Business Set-Aside (FAR 19.5). Place of performance: California 93436. Solicitation number 15B61727Q00000002.

Solicitation details

General information

Solicitation number
15B61727Q00000002
Notice type
Combined Synopsis/Solicitation
Set-aside
Total Small Business Set-Aside (FAR 19.5)
Place of performance
California 93436

Classification

NAICS
332321Metal Window and Door Manufacturing
Product or service
1290Miscellaneous Fire Control Equipment

Agency

Department
Department of Justice
Sub-tier
Federal Prison System / Bureau of Prisons
Office
FCC Lompoc

Description

From SAM.gov

                                                   STATEMENT OF WORK / REQUEST FOR QUOTE
A. INTRODUCTION:


1. The Federal Bureau of Prisons (FBOP), FCC Lompoc, 3901 Klein Blvd., Lompoc, CA 93436, is
seeking quotes from qualified vendors for the supply and delivery of nine (9) complete fire
escape door assemblies, including doors, frames, and all required hardware. The doors are for a
prison facility application and must meet all relevant local, state, and federal fire and life safety
codes.


2. "Equal or Better" Product Substitution: Proposals must meet or exceed the specified product
quality. If an alternative product or component is offered, the vendor must submit all technical
documentation, certifications, and test results for consideration.


3. Government's Right of Final Technical Acceptance: The government retains the sole and final
authority to determine technical acceptance for all submitted products, based on the provided
documentation and compliance with stated standards.


B. SCOPE OF WORK:


1. The vendor shall provide all materials as specified below. All components must be new, U.L.
Listed or labeled by a recognized testing agency acceptable to the Authority Having Jurisdiction
(AHJ) and conform to the standards referenced herein.


C. TECHNICAL SPECIFICATIONS:


TABLE 1: COMPONENTS: All units shall be identical unless otherwise noted.

  • Component
    • Requirement
  • Quantity
    • 9 Complete Door Assemblies
  • Door Size
    • 36" wide x 80" high x 2" thick
  • Door Material
    • Hollow Metal Door, minimum 12 Gauge galvanneal steel
  • Core
    • Ribbed and Insulated (mineral core for fire rating is acceptable/preferred)
  • Fire Rating
    • Rating must be compatible with the wall's fire resistance rating, typically 75% of the wall's rating. See required fire rating for correctional facilities on Table 2
  • Handing
    • 4 Left Hand Outswing, 5 Right Hand Outswing.
  • Frame Material
    • Minimum 12 Gauge galvanneal steel, fire-rated and labeled
  • Frame Type
    • Knock-down (KD) for drywall/unit masonry or welded for masonry. Frames are

to be prepared for 80 series lock, keyed 2 sides strike, surface pull on both
sides and prepped for PA closer.

  • Finish
    • Factory primed for field painting


TABLE 2: FIRE RATING:


The complete door assembly (door, frame, and all hardware) shall be 90 minutes fire rated. This rating
must be compatible with the fire-resistance rating of the specific wall assembly in which the door will be
installed, as dictated by the building's fire safety plan and local code requirements.
Category Requirement Description Applicable Standards &
Agencies

  • Listing & Labeling
    • All components must be listed and labeled by a recognized third-party testing agency acceptable to the Authority Having Jurisdiction (AHJ).
    • Underwriters Laboratories (UL), Intertek (WH), Factory Mutual (FM)
  • Testing Standard
    • Assemblies shall be tested under positive pressure conditions.

NFPA 252, ANSI/UL 10C

  • Labeling Visibility
    • A permanent, legible fire rating label must be affixed to both the door and the frame and remain visible after installation for inspection purposes.
    • N/A
  • Code Compliance
    • Vendor must confirm that all components, when installed as an assembly, comply with relevant building and safety codes for correctional facilities (Group I-3 Occupancies, IBC).
    • NFPA 80 (Standard for Fire Doors and Other Opening Protectives)
    • International Building Code (IBC)


TABLE 3: HARDWARE SPECIFICATIONS:


All hardware must be "listed" or "labeled" for use on a fire-rated assembly, compatible with the specified fire rating, and factory-prepped for ANSI/BHMA Grade 1 standards.


Item Requirement Quantity
per Door
Notes

  • Hinges
    • Heavy-duty steel ball bearing hinges, UL Listed
    • 3
  • Exit Device
    • Panic Hardware/Fire Exit Hardware (rim or mortise type) self-latching
    • 1 set
    • Must be a crossbar or touch bar device, operable with an applied force of 15 lbs or less.
  • Locking
    • Must be openable from the egress side at all times without special knowledge or tools. Keyed access from the exterior is permitted.
    • 1 set
    • 80 series lock, keyed 2 sides strike, surface pull on both sides and prepped for PA closer.
  • Door Closer
    • Heavy-duty, adjustable, surface-mounted, UL Listed
    • 1 unit
    • Must be self-closing and ensure positive latching.
  • Seals
    • Smoke and draft control gasketing/seals
    • 1 set
    • Required for a complete smoke-rated assembly.
  • Threshold
    • [Specify if required, e.g., 1/2" beveled aluminum, non-combustible]
    • 1 unit (if required)


D. CODE AND STANDARD REQUIREMENTS:


1. All supplied materials and the complete assembly must comply with the latest editions of the
following codes and standards (or local equivalents as adopted by the AHJ):

  • NFPA 80: Standard for Fire Doors and Other Opening Protectives
  • NFPA 101: Life Safety Code
  • International Building Code (IBC)
  • International Fire Code (IFC)
  • OSHA requirements for exit routes
  • UL 10C or NFPA 252: Standard for positive pressure fire testing of door assemblies
  • UL 1784: Standard for Air Leakage Tests of Door Assemblies (if smoke rating is required)


2. Vendors must confirm that all components, when installed as an assembly, will bear a permanent,
legible label from a recognized third-party testing agency (e.g., UL, Intertek/WH, FM).


E. SUBMISSION REQUIREMENTS:


1. Itemized pricing for doors, frames, hardware, and any included accessories.
2. Proposed lead time for manufacturing and delivery to FCC Lompoc
3. Confirmation of compliance with all referenced codes and standards.
4. Cut sheets/product data for all proposed items.


F. DELIVERY OF MATERIALS:


1. Deliveries shipped directly to FCC LOMPOC can only be received between 7:30 a.m. and 2:00
p.m., Monday through Friday, excluding Federal Holidays.


2. POC: Mr. Fernando Pena, BOP Engineering Technician, FXPena@bop.gov, or 805-735-2771


3. FBOP will be responsible for receiving or signing deliveries.


4. FCC LOMPOC will provide resources for loading and unloading materials or equipment upon
arrival.

Documents

3 files

Sign up free to download these 3 files.

  • 15B61727Q00000002-BRQ.pdf
    163 KB · Nov 5, 2026
    Download
  • FCC Lompoc Fire Door Assembly Combined Synopsis.pdf
    190 KB · Nov 5, 2026
    Download
  • LOX 26Z6AL1 RplFireEscapeDoors FCI 1_SOW_Approved..pdf
    222 KB · Nov 5, 2026
    Download

Similar open bids

Same NAICS 332321

More from Bureau of Prisons

Open bids, other NAICS codes